400kva Online UPS Low Frequency Ups With Isoltion Transformer For Big IDC Center Online UPS
Model | GX9335C | ||||||||||
Rectifier Type | 6p | 12p | 6p | 12p | 6p | 12p | 6p | 12p | 6p | 12p | |
Rated Nominal | 120KVA/108KW | 160KVA/144KVA | 200KVA/180KW | 300KVA/270KW | 400KVA/360KW | ||||||
Rated input voltage | 380/400/415VAC 3-phase 4-wire | ||||||||||
Rated frequency | 50/60HZ | ||||||||||
Input parameters | |||||||||||
Input voltage range | ±25% | ||||||||||
Input frequency range | 45Hz~65Hz | ||||||||||
Input soft start function | 0-100% 5-300settable | ||||||||||
Input power factor | >0.98(If harmonic filter is added) | ||||||||||
Input harmonic current (THDi) | ‹4.5%(If harmonic filter is added) | ||||||||||
Bypass | |||||||||||
Bypass voltage range | -20%~+15% | ||||||||||
Bypass frequency range | 50/60HZ±10% | ||||||||||
Output parameters | |||||||||||
Inverter output voltage | 380/400/415VAC 3-phase 4-wire | ||||||||||
Voltage stability | ±1%(Steady status),±3%(Transient status) | ||||||||||
Frequency | 50/60Hz | ||||||||||
Mains power synchronization window | ±5% | ||||||||||
Actually measured frequency accuracy (internal clock) | 50/60Hz±0.01Hz | ||||||||||
Output power factor | 0.9(Output 90kW per 100kVA) | ||||||||||
Transient response time | <5ms | ||||||||||
Inverter overload capability | At 0.9 power factor, 110% for 1 hour, 125% for 10 minutes and 150% for 60s | ||||||||||
3ph 1.5ln for 5seconds,1ph 2.9ln for 5seconds | |||||||||||
Short circuit current from inverter | |||||||||||
Maximum Bypass capability | 1000% for 100ms | ||||||||||
With 100% balanced load | <1° | ||||||||||
Phase shift | |||||||||||
characteristic | With 100% imbalance load | <1° | |||||||||
100% linear load | <1% | ||||||||||
Total harmonic | |||||||||||
Distortion(THDv) | 100% non-linear load | <3% | |||||||||
System efficiency (full load) | Up to 94% (inverter efficiency is up to 98%) | ||||||||||
Rectifier output parameters | |||||||||||
Charger output voltage stability | 1% | ||||||||||
DC ripple voltage | ≤1% | ||||||||||
Operating environment | |||||||||||
Operating temperature range | 0~40°C | ||||||||||
Storage temperature | -25~70°C(Without battery) | ||||||||||
Relative humidity | 0~95% No condensation | ||||||||||
Noise (1m) | 58-68dB | ||||||||||
Protection level | IP20 | ||||||||||
Standard | Safety: IEC60950-1 IEC62040-1-1 UL1778 EMC IEC62040-2 CLASS C2 EN50091-2 CLASS A Design and Test IEC62040-3 |