Phase: | Single Phase |
---|---|
Type: | On-line |
Protection: | Overvoltage |
Application: | Industry |
Classification: | Lighting/Power |
Standby Time: | Standard Machine |
Customization: |
---|
Suppliers with verified business licenses
Typical application
Data center, bank station, network, communication equipment, office, automatic equipment, monitor equipment, control system.
Highly flexible and extendable
Charge current can be adjusted.
Standard charge current 4A.
Support more discharge time and more capacity battery for 8A charger.
Input topology design
Support three-phase input or single-phase input for three-phase UPS.
Super wide input voltage and frequency range suitable for bad grid environment.
Digital control DSP technology and the best power component make the system safe and reliable.
Multifunction friendly design and Advanced parallel technology
Stable parallel control technology makes sure current sharing to 1%.
Select trip technology can avoid and isolation system faults and then improve system availability.
Flexible extension capacity and redundancy management that can satisfy all kinds of requirements.
Support maximum 3 units for parallel working.
Flexible strategy
Online mode provides higher system availability.
High-efficiency mode provides more economic operation.
Frequency conversion provides more stable output.
Higher function
Output power factor up to 0.9
Output power factor is 0.9 which means can take more load, if you take the same load it can get higher reliability.
Input power factors up to 0.99
Three-phase input model supports three-phase PFC, input THDl<5%.
Output voltage regulation 1%, frequency regulation 0.1%, parallel current sharing 1%.
The efficiency up to 94%
Efficiency up to 93.5%when take the 30%load.
ECO mode efficiency up to 98%.
Model | HX9116C PLUS 6-10KVA | |||
Power Capacity(VAW) | 6KS | 6K-XL | 10KS | 10K-XL |
Rated Power | 6KVA/5.4KW | 10KVA/9KW | ||
Rated Voltage | 220VAC | |||
Rated Frequency | 40-70 Hz | |||
Input | ||||
Voltage Range | 120~275VAC(±3VAC) | |||
THDi | <5% | |||
Power Factor | ≥0.99 | |||
Output | ||||
Voltage Regulation | 220±1%VAC | |||
Frequency Regulation | 50/60 Hz±0.2Hz | |||
Waveform | Pure sine wave | |||
Power Factor | 0.9 | |||
THDV | Linear load<2%Non-linear load<4% | |||
Efficiency | >94% | |||
Current Crest Ratio | 3:1 | |||
Transfer Time | 0ms(AC mode→Battery mode) | |||
Battery | ||||
DC Voltage | 180VDC | 192VDC | 192VDC | |
Recharge Time | 5hrs to 90%of capacity | |||
Recharge Current | 1A | 4.2A | 1A | 4.2A |
Display | ||||
LCD | Mode/FaultWarning/Display input/output Voltage,Frequency,Battery voltage,Battery capacity,Loading rate | |||
Communication | ||||
Interface | Smart RS232,SNMP(Optional),USB(Optional) | |||
Environment | ||||
Operation Temperature | 0~40ºC | |||
Humidity | 0~95%(Non-condensing) | |||
Storage Temperature | -25ºC~55ºC | |||
Operation Altitude | <1000m | |||
Noise Level (1m) | <55dB | |||
Physics Characteristic | ||||
Weight(KG) | 59 | 14 | 62 | 16 |
Dimensions:(Wx DxH)mm | 248X500X616 | 212X500X420 | 248X500X616 | 212X500X420 |