Customization: | Available |
---|---|
Phase: | Single Phase |
Type: | Line Interactive |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Typical application
Data centre, bank station, network , communication equipment, office, automatic equipment, monitor equipment, control system
Highly flexible and extendable
Battery can choose
1. Battery voltage can be choice depend on capacity , can satisfy different requirement.
2. Convenience to get more back up time and lower system invests
3. Convenience to save cost of battery
4. Intelligent battery monitors Charge current can be adjust
5. Standant charge current 4A
6. Support more discharge time and more capacity battery for 8A charger
Input topology design
7. Support three phase input or single phase input for three phase UPS
8. Super wide input voltage and frequency range suitable for bad power electirc environment
9. Digital control DSP technology and best power component make the system safe and reliable
Multifunction friendly design
Advanced parallel technology
1. Stable parallel control technology make sure current sharing to 1%
2. Select trip technology can avoid and isolation system fault then improved system availability
3. Flexible extension capacity and redundance management that can satisfy all kinds of requirements
4. Support maximum 3 units for parallel working
Flexible strategy
5. On line mode provides higher system availability
6. High efficiency mode provides more economic operation
7. Frequency conversion provides more stable output
Higher function
Output power factor up to 0.9
1. Output power factor is 0.9 that mean can take more load, if you take same load that can get higher reliability. Input power factors up to 0.99
2. Three phase input model support three phase PFC , input THDI<5%
3. Output voltage regulation 1%, frequency regulation 0.1%, parallel current sharing 1%.
The efficiency up to 94%
4. Efficiency up to 93.5%when take the 30%load
5. ECO mode efficiency up to 98%
PHASE | Single phase with ground | ||||||||
CAPACITY | 1000VA/800W | 2000VA/1600W | 3000VA/2400W | 6000VA/4800W | 10000VA/8000W | ||||
INPUT | |||||||||
Nominal Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC | 208/220/230/240VAC | |||||||
Input Voltage Range | 55-145VAC or 110-300VAC at50%load 85-140VAC or 160-280VAC a t 100%load |
110-300VAC±3%at 50%load 176-300VAC±3%a t100%load |
|||||||
Frequency Range | 40Hz-70Hz | 46Hz~54Hz OR 56Hz~64 Hz | |||||||
Power Factor | 0.99@100%load | ||||||||
OUTPUT | |||||||||
Output Voltage | 00/110/115/120/127VACor 200/208/220/230/240VAC | 208/220/230/240VAC | |||||||
Voltage Regulation | ±1% | ±1% | |||||||
Frequency Range (Synchronized Range | 47~53 Hz or 57~~63 Hz | 46Hz~54Hzor 56Hz~64 Hz | |||||||
Frequency Range(Batt.Mode) | 50Hz±0.25Hzor 60Hz±0.3 Hz | 50Hz±0.1Hzor 60Hz±0.1Hz | |||||||
Current Crest Ratio | 3:1 | ||||||||
Harmonic Distortion | =3 %THD (Linear Load),≤5 %THD (Non-linear Load) | ||||||||
Transfer Time |
AC Mode to Battery Mode | 0ms | |||||||
Inverter to Bypass | 4 ms(Typical ) | 0 ms | |||||||
Waveform (Batt.Mode) | Pure Sinewave | ||||||||
EFFICIENCY | |||||||||
AC Mode | 88% | 89% | 90% | 929% | 93% | ||||
Battery Mode | 83% | 87% | 88% | 90% | 91% | ||||
BATTERY | |||||||||
Standard Model |
Battery Type | 12V/9AH | 12V/9 AH | 12V/7 AH | |||||
Numbers | 2 | 4 | 6 | ||||||
Typical Recharge Time | 4 hours recover to 90% capacity | ||||||||
Charging Current | 1.0A | ||||||||
Charging Voltage | 27.4VDC±1% | 54.7VDC±1% | 82.1VDC±1% | ||||||
Long-run Model |
Battery Type | Depending on the capacity of external batteries | |||||||
Numbers | 3 | 6 | 8 | 16~20(Adjustable) | |||||
Charging Current (max. | 1.0A/2.0A/4.0A/6.0 A | 1A/2A/4A/6A Adjustable | |||||||
Charging Voltage | 41.0VDC ±1% |
82.1VDC ±1% |
109.4VDC ±1% |
218.4VDC±1%(Baed on 16pic batteries) | |||||
NDICATORS | |||||||||
LCD Panel | UPS status,Load level,Battery level,Input/Output voltage,Discharge timer,and Fault conditions | ||||||||
ALARM | |||||||||
Battery Mode | Sounding every 4 seconds | ||||||||
Low Battery | Sounding every second | ||||||||
Over load | Sounding twice every second | ||||||||
Fault | Continuously sounding | ||||||||
PHYSICAL | |||||||||
Standard Model |
Dimension,DxWxH(mm) | 310x438x88[2U] | 410x438x88[2U] | 630x438x88[2U] | |||||
Net Weight (kgs | 12 | 19 | 293 | ||||||
Long-run Model |
Dimension,DxWxH (mm) | 310x438x88[2U] | 410x438x 88[2U] | 500x438x88[2U] | 580x 438x133[3U] | ||||
Net Weight (kgs | 9 | 12 | 142 | 15 | 18 | ||||
ENVIRONMENT | |||||||||
Humidity | 20-90%RH @0-40ºC(non-condensing | 0-95 %RH @0-40ºC(non-condensing) | |||||||
Noise Level | Less than 50dB @1 Meter | Less than 55dB@1 Meter | Less than 58dB @1Meter | ||||||
MANAGEMENT | |||||||||
Smart RS-232/USB | Supports Windows"2000/2003/XPMista/2008,Windows"7/8,Linux,Unix,and MAC | ||||||||
Optional SNMP | Power management from SNMP manager and web browser |