Phase: | Single Phase |
---|---|
Type: | On-line |
Protection: | Overvoltage |
Application: | Industry |
Classification: | Lighting/Power |
Standby Time: | Standard Machine |
Customization: |
---|
Suppliers with verified business licenses
HX9335C Plus 10-30KVA
Model:10-30KVA
Nominal voltage:380/400/415VAC
Nominal frequency:50/60Hz
Output Power factor:0.9
Key Features:
True double-conversion.
DSP technology guarantees high performance.
Output power factor 0.9.
Active power factor correction in all phases.
50Hz/60Hz frequency converter mode.
ECO mode operation for energy saving.
Accepts dual mains inputs.
Emergency power off function (EPO).
Generator compatible.
SNMP+USB+RS-232 multiple communications.
3-stage extendable charging design for optimized battery performance.
Adjustable battery numbers.
Maintenance bypass available.
Optional N+X parallel redundancy.
Optional isolation transformer offers full isolation and complete common-mode noise rejection.
Reduce the investment cost saving valuable space:
HP9335C Plus Series UPS represents the best solution that is both cost-effective and environmentally friendly, It delivers excellent integrated autonomy, reduced footprint, and optimum input and output performances, guaranteeing reliable and flexible power.
MODEL | HX9335C Plus 10-30KVA | ||||||||
10K | 10K-XL | 15K | 15K-XL | 20K | 20K-XL | 30K | 30K-XL | ||
CAPACITY | 10KVA/9KW | 15KVA/13.5KW | 20KVA/18KW | 30KVA/24KW | |||||
PHASE | 3 Phase with Neutral | ||||||||
INPUT | |||||||||
Voltage Range | Low Line Loss | 290-498 VAC | |||||||
Phase | Three phase with ground | ||||||||
Power Factor | ≥0.99 at 100%Load | ||||||||
OUTPUT | |||||||||
Output voltage | 208/220/230/240VAC(Ph-N) | ||||||||
AC Voltage Regulator | ±1% | ||||||||
Frequency Range (Synchronized Range) | 46Hz~54 Hz @50Hz system;56Hz~64 Hz @60Hz system | ||||||||
Frequency Range (Batt. Mode) | 50 Hz±0.1 Hzor 60Hz±0.1 Hz | ||||||||
Overload | AC mode | 100%~110%:10min;110%~125%:1min;>150%:1sec | |||||||
Battery mode | 100%~110%:30sec;110%~125%:10sec;>150%:1sec | ||||||||
Current peak factor | 3:1 max | ||||||||
Harmonic Distortion | ≤2 %@100%Linear Load;≤5 %@100%Non-linear Load | ||||||||
Transfer Time |
Line←→Battery | 0 ms | |||||||
Inverter→Bypass | 0 ms (When phase lock fails,<4ms interruption occurs from inverter to bypass) | ||||||||
Line→ECO <10 ms | |||||||||
Efficiency | up to 92.5% | ||||||||
BATTERY | |||||||||
Standard Model |
Type | 12V/9 Ah | 12V/9 Ah | 12V/9 Ah | 12V19 Ah | ||||
Numbers | 20(18-20 adjustable) | 2x20(18-20 adjustable) | 2x20(18-20 adjustable) | 3x20 | |||||
Recharge Time | 9 hours recover to 90%capacity | ||||||||
Charging Current | 1.0 A±10%(max.) | 2.0A±10%(max.) | 2.0 A±10%(max.) | 4.0A±10%(max. | |||||
Charging Voltage | 273 VDC±1% | ||||||||
Long-run Model |
Type | Depending on applications | |||||||
Numbers | 18-20 | ||||||||
Charging Current | 4.0 A±10%(max.) | 4.0 A±10%(max.) | 4.0 A±10%(max.) | 12.0A±10%(max | |||||
Charging Voltage | 273VDC±1% | ||||||||
PHYSICAL | |||||||||
Standard Mode | Dimension,DxWxH(mm) | 832 X250X894 | 832 X250X1275 | ||||||
Long-run Model | Dimension,DxWxH(mm) | 609 X250X768 | 832 X250X828 | ||||||
ENVIRONMENT | |||||||||
Operation Temperature | 0~40ºC(the battery life will down when>25ºC) | ||||||||
Operation Humidity | <95 %and non-condensing | ||||||||
Operation Altitude | <1000m | ||||||||
Acoustic Noise Level | Less than 58dB @1 Meter | Less than 60dB @1 Meter | |||||||
MANAGEMENT | |||||||||
Smart RS-232/USB | Supports Windows 2000/2003/XPMista/2008,Windows 7 | ||||||||
Optional SNMP | Power management from SNMP manager and web browser |
Suppliers with verified business licenses