Customization: | Available |
---|---|
Phase: | Three Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introduction:
FM33 20-180kVA uses frame design, suitable for standard 19 inches network cabinet. It adopts online double conversion technology, which can completely eliminate all kinds of grid problems and provide customers with stable and pure sinusoidal power supply protection.
Scenarios:
Standard 19 inches network cabinet of computer room, IDC room, integrated comprehensive cabinet, etc.
Features:
1.Frame mounted design
2.Wide input voltage range
3.Online double conversion and three level technology
4.DSP digital control technology
5.Output power factor 0.9
6.N+X redundancy
7.Communications: RS485/Relay card/USB/SNMP option
8.The number of battery cells is 30-50 adjustable
Benefits:
1.Wide input voltage range adapt to harsh power grid
2.DSP technology greatly improve the system reliability
3.4.3-inch color touch screen, graphic display, easy to operate
4.Intelligent battery management extend battery life
Model | |||||
Capacity | Frame | 20~60kVA | 20~120kVA | 20~180kVA | |
Module | 20kVA/25kVA/30kVA | ||||
Max. Module Number | 2 | 4 | 6 | ||
Input | Phase | 3 Phase 4 Wires and Ground | |||
Rated Voltage | 380/400/415Vac | ||||
Voltage Range | 138~485Vac | ||||
Frequency Range | 40Hz-70Hz | ||||
Power Factor | ≥0.99 | ||||
Current THDi | ≤3%(100% linear load) | ||||
Bypass Voltage Range | Max.voltage: 220V:+25 %( optional +10%, +15%, +20%); 230V:+20 %( optional +10%, +15%); 240V:+15 %( optional +10%);Min. voltage: -45% (optional -20%,-30%) | ||||
Frequency protection range: ±10% | |||||
Generator access | Yes | ||||
Output | Phase | 3 Phase 4 Wires and Ground | |||
Rated Voltage | 380/400/415Vac | ||||
Power Factor | 0.9 or 1 | ||||
Voltage Regulation | ±1% | ||||
Frequency | Utility Mode | ±1%,±2%,±4%,±5%,±10% of the rated frequency(optional) | |||
Battery Mode | (50/60±0.1%)Hz | ||||
Crest Factor | 3:1 | ||||
THD | ≤2% with linear load, ≤5% with non linear load | ||||
Efficiency | 96% | ||||
Overload | ≤ 110%: to bypass after 60 min, ≤ 125%: to bypass after 10 min, ≤ 150%: to bypass after 1 min | ||||
Battery | Voltage | ±180V/192V/±204V/±216V/±228V/±240/±252/±264/±276/±288/±300Vdc(30/32/34/36/38/40/42/44/46/48/50pcs optional) | |||
Charging Current | UPS Cabinet | 20A Max. | 40A Max. | 60A Max. | |
UPS Module | 10A Max. | ||||
Transfer Time | Utility to Battery : 0ms; Utility to bypass: 0ms | ||||
Protection | Alarm | overload, utility abnormal, UPS fault, battery low, etc | |||
Protection | short circuit, overload, over temperature, battery low, fan fault alarm | ||||
Communication Interface | RS232, RS485, Intelligent slot x 2, Dry Contact,SNMP | ||||
Environment | Operating Temperature | 0ºC~40ºC | |||
Storage Temperature | -25ºC~55ºC | ||||
Humidity | 0~95% non condensing | ||||
Altitude | < 1500m | ||||
Other | Unit Dimensions(D*W*H) | Frame | 780x485x487 | 780x485x663 | 810x485x755 |
Module | 620x440x86mm | ||||
Weight (Kg) | Frame | 45 | 60 | 80 | |
Module | 20.8/21/21 | ||||
Standards | EN62040-1, EN62040-2 |