Customization: | Available |
---|---|
Phase: | Single Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
HX9335CR PLUS 10-20KVA
Model:10-20KVA
Nominal voltage:380/400/415VAC
Nominal frequency:50/60Hz
Output Power factor:0.9
Key Features:
True double-conversion.
DSP technology guarantees high performance.
Output power factor 0.9.
Active power factor correction in all phases.
50Hz/60Hz frequency converter mode.
ECO mode operation for energy saving.
Accepts dual mains inputs.
Emergency power off function (EPO).
Generator compatible.
SNMP+USB+RS-232 multiple communications.
3-stage extendable charging design for optimized battery performance.
Adjustable battery numbers.
Maintenance bypass available.
Optional N+X parallel redundancy.
Optional isolation transformer offers full isolation and complete common-mode noise rejection.
Reduce the investment cost saving valuable space:
HP9335C Plus Series UPS represents the best solution that is both cost-effective and environmentally friendly, It delivers excellent integrated autonomy, reduced footprint, and optimum input and output performances, guaranteeing reliable and flexible power.
MODEL | HX9335CR PLUS 10-20KVA | |||
10K-XL | 15K-XL | 20K-XL | ||
CAPACITY | 10KVA/9KW | 15KVA/13.5KW | 20KVA/18KW | |
PHASE | 3 Phase with Neutral | |||
INPUT | ||||
Voltage Range | Low Line Loss | 290-498 VAC | ||
Phase | Three phase with ground | |||
Power Factor | ≥0.99 at 100%Load | |||
OUTPUT | ||||
Output voltage | 208/220/230/240VAC(Ph-N) | |||
AC Voltage Regulation | ±1% | |||
Frequency Range (Synchronized Range | 46Hz~54 Hz @50Hz system;56Hz~64 Hz @60Hz system | |||
Frequency Range (Batt.Mode) | 50 Hz±0.1 Hz or60Hz±0.1 Hz | |||
Overload | AC mode | 100%~110%:10min;110%~125%:1min;>150%:1sec | ||
Battery mode | 100%~110%:30sec;110%~125%:10sec;>150%:1sec | |||
Current peak factor | 3:1 max | |||
Harmonic Distortion | ≤2 %@100%Linear Load;≤5 %@100%Non-linear Load | |||
Transfer Time |
Line→Battery | 0 ms | ||
Inverter→Bypass | 0 ms(When phase lock fails,<4ms interruption occurs from inverter to bypass) | |||
Line→ECO <10 ms | ||||
Efficiency | up to 92.5% | |||
BATTERY | ||||
Standard Model |
Type | 12V/9 Ah | ||
Numbers | 2x20(18-20 adjustable) | |||
Recharge Time | 9 hours recover to 90%capacity | |||
Charging Current | 1.0 A±10%(max.) | 2.0A±10%(max.) | ||
Charging Voltage | 273 VDC±1% | |||
Long-run Model |
Type | Depending on applications | ||
Numbers | 18-20 | |||
Charging Current | 4.0 A±10%(max.) | |||
Charging Voltage | 273 VDC±1% | |||
PHYSICAL | ||||
Dimension,DxWxH(mm) | 725mm*438mm*266mm | |||
ENVIRONMENT | ||||
Operation Temperature | 0~40ºC(the battery life will down when>25ºC) | |||
Operation Humidity | <95 %and non-condensing | |||
Operation Altitude | <1000m | |||
Acoustic Noise Level | Less than 58dB @1 Meter | Less than 60dB @1 Meter | ||
MANAGEMENT | ||||
Smart RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008,Windows / | |||
Optional SNMP | Power management from SNMP manager and web browser |